DRN4 VERSION #2 - ACI
Automation Field Components
PWM/Analog/Floating Point to Resistance Output, 0 to 135 Ohm Resistance Network, Version 2, Plastic Enclosure
This item is temporarily out of stock.
It can be backordered right now, and we can ship it within 5 weeks.
0
131479
ACI
U.S.A.
{{CMP.TITLE}}
- Features
- Comments (0)
-
Data Sheet
DRN4 VERSION #2 - ACI
Automation Field Components
download pdfPlease contact us if you need any other document this item may have.
You can only download Technical Document (Datasheet) on this section.
The DRN4 is a resistive output motor actuator interface that accepts several types of DDC system signals. The DRN4 output is 0 to 135 ohms. The input signal types are field selectable by an 8-position DIP switch. The floating point input accepts two digital signals, one for increase and the other for decrease. The floating point full scale rate of change is 55 seconds. Some triac input signals require an accessory. The DRN4 is supplied in an enclosure that can be directly mounted to a 1/2 inch knockout on the motor acuator. Color coded wire leads with spade connectors are provided for electrical connections. The DRN4 is covered by ACI's Two (2) Year Limited Warranty.
- Resistive sensor simulation
- Electronic potentiometer
- Electric Actuator control
Warranty :This product is under warranty for 2 years against manufacturing and material defects from the date of invoice. The invoice for the products also stands in place of the warranty certificate, a separate document is not issued.Delivery Information :ACI branded products are imported from United States of America factory specially to order. The estimated delivery time of the products is 5 weeks. In this product group, an additional shipping and customs fee of 450EUR is charged for orders under 4,000EUR.
A/20K-INW-4'-BB - ACI
Automation Field Components
20,000 Ohm Thermistor, Immersion, No Well, 4', NEMA 3R Enclosure
A/AN-R2SO-A10-C5 - ACI
Automation Field Components
10,000 Ohm Thermistor (Type III), Room (R2), Setpoint 0 to 1K Ohms, Override, Cool/Warm Sticker
BN2110-INW-2.5-PB - ACI
Automation Field Components
BACnet MS/TP, Modbus RTU, Temperature, Immersion No Well, 2.5", Plastic Enclosure
A/RH2-TTM1K-D-4X-2 - ACI
Automation Field Components
Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Duct, NEMA 4X Enclosure, ± 2% Accuracy (NIST Cert), Transmitter w/ 1,000 Ohm RTD (NIST Cert), 2-10VDC (Temp Output)
A/DLP-001-W-U-D-A-0 - ACI
Automation Field Components
Differential Pressure, (0.5% Acc), 0.1, 0.2, 0.5, 1 inWC (Default) , LCD, Unidirectional (Default), Bidirectional (Selectable)
A/RH5-SP-05 - ACI
Automation Field Components
Relative Humidity, RH Outputs: 0-5 VDC, Wall Plate 304SS, ± 5% Accuracy, 0-5VDC Output
A/1K-3W-HT-BP-8' - ACI
Automation Field Components
1,000 Ohm (Three Wires) RTD, High Temperature Bullet Probe, 1", 316SS, 8'
A/100-3W-SP - ACI
Automation Field Components
100 Ohm (Three Wires) RTD, Wall Plate, Stainless Steel