A/RH5-TT1K-R-1 - ACI
Automation Field Components
Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Room (R), ± 5% Accuracy, Transmitter w/ 1,000 Ohm RTD, 1-5VDC Output
This item is temporarily out of stock.
It can be backordered right now, and we can ship it within 5 weeks.
0
146794
ACI
U.S.A.
{{CMP.TITLE}}
- Features
- Comments (0)
-
Data Sheet
A/RH5-TT1K-R-1 - ACI
Automation Field Components
download pdfPlease contact us if you need any other document this item may have.
You can only download Technical Document (Datasheet) on this section.
The ACI Relative Humidity with Temperature Transmitter Room Series utilizes a thermoset polymer capacitive sensing element with a factory applied hygroscopic lter to deliver a proportional analog current or voltage output signal. The hygroscopic lter provides added resistance to moisture, dust, and other chemicals for greater long term reliability. The RH Room transmitter features integral DIP switches for eld selection of the proper output signal and supply voltage to meet your applications requirements. Each unit also contains 0%, 50%, and 100% test options to verify that the transmitter is both working and wired properly. Field calibration can be performed by using the increment and decrement calibration DIP switches without the need to replace the sensing element. These enhancements provide increased exibility and outstanding long-term reliability. The temperature transmitter must be powered with 13.5 to 24 VDC power source and can be ordered as either a two-wire 4-20 mA or 3-wire voltage output sensor. The temperature transmitter is installed on the back of the enclosure and must be mounted over a single gang junction box in the wall. There are two styling options in this series which should satisfy most commercial decors. Both styles feature four-way airow to minimize self-heating. NIST Calibration Certicates are available for all RH TTM part series. Applications: Monitor Room RH Levels, Humidication, Dehumidication, Hospitals, Clean Rooms, Oce Buildings, Schools, Museums, Process Control, ESD (Anti-Static) Control, Data Centers
Warranty :This product is under warranty for 2 years against manufacturing and material defects from the date of invoice. The invoice for the products also stands in place of the warranty certificate, a separate document is not issued.Delivery Information :ACI branded products are imported from United States of America factory specially to order. The estimated delivery time of the products is 5 weeks. In this product group, an additional shipping and customs fee of 450EUR is charged for orders under 4,000EUR.
A/M6' - ACI
Automation Field Components
6' Thermowell, 1/2 NPT, 304 SS Machined
A/AN-BC-D-12'-PB - ACI
Automation Field Components
10,000 Ohm Thermistor w/11K Shunt, Duct, 12', Plastic Enclosure
A/100-2W-D-18'-GD - ACI
Automation Field Components
100 Ohm (Two Wires) RTD, Duct, 18', Galvanized Enclosure
TUC2-16-F2-1E-G0-X-X-X-X - ACI
Automation Field Components
LCD, SET, DEG F
A/DLP-004-W-B-D-B-0-A-3P-S - ACI
Automation Field Components
Differential Low Pressure, 4 inWC, Bidirectional, LCD, 0.25% Accuracy, No Pitot Tube, 4-20mA Output, 3 Point Nist, Standard
A/1K-NI-PM-NIST - ACI
Automation Field Components
1,000 Ohm Nickel RTD, Pipe Mount, Brass, NIST Cert
A/TT1K-R2S-2-B/R - ACI
Automation Field Components
Transmitter w/ 1,000 Ohm RTD, Room (R2) with Setpoint, 2-10VDC Output, B/R
A/RH3-10K-E1-D-BB - ACI
Automation Field Components
Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Duct, ± 3% Accuracy, 10,000 Ohm (E1) Thermistor, NEMA 3R Enclosure