Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Room (R), ± 2% Accuracy, 10,000 Ohm Thermistor (Type II), Setpoint:0-100K, w/ Override
This item is temporarily out of stock.
It can be backordered right now, and we can ship it within 5 weeks.
0
142907
ACI
U.S.A.
{{CMP.TITLE}}
- Features
- Comments (0)
-
Data Sheet
A/RH2-CP-RSO-A01-C5 - ACI
Automation Field Components
download pdfPlease contact us if you need any other document this item may have.
You can only download Technical Document (Datasheet) on this section.
The ACI Relative Humidity with Thermistor Room Series utilizes a thermoset polymer capacitive sensing element with a factory tted hydrophobic lter to improve its moisture resistance. The sensing elements multilayer construction also provides excellent resistance in applications where dust, dirt, oils and common environmental chemicals are found. The RH room sensors include on board DIP switches which allow the user to select the desired output signal and can be powered by AC or DC power sources. Single point eld calibration can be performed by using the increment and decrement calibration DIP switches to adjust your curve up or down in +/- 0.5% increments with each toggle of the corresponding switches. These enhancements provide increased exibility and outstanding long-term reliability without the need to replace the sensors in the eld. There are two enclosure options in this series which should satisfy most commercial decors. Both enclosures feature four-way airow to minimize self-heating. Three point NIST Calibration Certicates are available. Applications: Humidication, Dehumidication, Monitoring Indoor Space Humidity, Clean Rooms, Hospitals, Process Control, Laboratories, Museums, Schools, Oce Buildings, Data Centers, ESD (Anti-Static) Control The ACI RH Thermistors Room is covered by ACI's Five (5) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com.
Warranty :This product is under warranty for 2 years against manufacturing and material defects from the date of invoice. The invoice for the products also stands in place of the warranty certificate, a separate document is not issued.Delivery Information :ACI branded products are imported from United States of America factory specially to order. The estimated delivery time of the products is 5 weeks. In this product group, an additional shipping and customs fee of 450EUR is charged for orders under 4,000EUR.
A/TT1K-D-6'-2-GD - ACI
Automation Field Components
Transmitter w/ 1,000 Ohm RTD, Duct, 6', Galvanized Enclosure, 2-10VDC Output
A/TTM100-D-8'-4-4X - ACI
Automation Field Components
Transmitter w/ 100 Ohm RTD (NIST Cert), Duct, 8', NEMA 4X Enclosure, 4-20mA Output
A/DLP-D25-W-B-N-B-1-C-3P-S - ACI
Automation Field Components
Differential Low Pressure, 0.25 inWC, Bidirectional, No Display, 0.25% Accuracy, w/ Pitot Tube, 0-10VDC Output, 3 Point Nist, Standard
A/20K-RSO-A03-C5 - ACI
Automation Field Components
20,000 Ohm Thermistor, Room (R), Setpoint 0 to 10K Ohms, Override, Cool/Warm Sticker
TUC2-16-F4-1E-G0-X-X-X-X - ACI
Automation Field Components
4-20mA Output, Setpoint, LCD
RN (200-1200) - ACI
Automation Field Components
Resistor Network (200 to 1200 Ohms)
A/RH3-TT100-R2-2 - ACI
Automation Field Components
Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Room (R2), ± 3% Accuracy, Transmitter w/ 100 Ohm RTD, 2-10VDC (Temp Output)
A/RH3-AN-R2-05 - ACI
Automation Field Components